| Plan Review Notes For Permit 11080524 |
| Permit Number |
11080524 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-25 09:09:48 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE EXPOSURE CATEGORY FOR THIS STRUCTURE IS "C" PER | | | FBC R301.2.1.4.2. PLEASE INCREASE THE OPENING PRESSURES | | | TO CORRESPOND WITH EXPOSURE CATEGORY C. | | | | | | 2) THE ALLOWABLE PRESSURES ON THE SHUTTER INSTALLATION | | | SCHEDULE ARE INCORRECT FOR THE ANCHORS, SPACING AND | | | OTHER CRITERIA LISTED IN THE PRODUCT APPROVAL. THE | | | ALLOWABLE PRESSURES DEPEND ON THE SUBSTRATE, MOUNT | | | TYPE, SPAN, EDGE DISTANCE, ANCHOR TYPE AND ANCHOR | | | SPACING. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|