2011-08-25 09:09:482007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY FOR THIS STRUCTURE IS "C" PER
 FBC R301.2.1.4.2. PLEASE INCREASE THE OPENING PRESSURES
 TO CORRESPOND WITH EXPOSURE CATEGORY C.
  
 2) THE ALLOWABLE PRESSURES ON THE SHUTTER INSTALLATION
 SCHEDULE ARE INCORRECT FOR THE ANCHORS, SPACING AND
 OTHER CRITERIA LISTED IN THE PRODUCT APPROVAL. THE
 ALLOWABLE PRESSURES DEPEND ON THE SUBSTRATE, MOUNT
 TYPE, SPAN, EDGE DISTANCE, ANCHOR TYPE AND ANCHOR
 SPACING. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW