| 2011-08-23 13:37:38 | 11080500 | | | 1320 WILDERNESS DR | | | FLORIDA ROOM RENOVATION | | | | | | PLEASE SUBMIT A PLAN SHOWING THE REQUIRED ELECTRICAL | | | OUTLETS FOR THE NEW LIVING AREA. | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | | 210.12 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 | | | THE NEW LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR | | | LIGHT AND A SWITCHED LIGHT AT OUTSIDE ENTRANCES. AT | | | LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED | | | OUTSIDE. NEC 210.70 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|