| Plan Review Notes For Permit 11080473 |
| Permit Number |
11080473 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-19 12:46:03 | 525 OKEECHOBEE BOULEVARD - 8TH FLOOR | | | PERMIT #11080473 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE SPRINKLERS AND FIRE ALARM NOTIFICATION APPLIANCES | | | WILL NEED TO BE ADDED AND/OR RELOCATED TO ACCOUNT FOR | | | THE NEW WALLS. SEPARATE PLANS AND PERMITS ARE REQUIRED | | | FOR THE INSTALLATION OR MODIFICATION OF THE FIRE | | | SPRINKLER SYSTEM AND FIRE ALARM SYSTEM. | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | | REMOVED FROM THE SITE DAILY. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF | | | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. | | | | | | EXIT SIGN LOCATIONS NOT INDICATED ON PLANS. FIELD | | | INSPECTOR MAY REQUIRE ADDITIONAL EXIT SIGNS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|