Plan Review Notes
Plan Review Notes For Permit 11080463
Permit Number 11080463
Review Stop B
Sequence Number 1
Notes
Date Text
2011-08-19 08:56:46BUILDING PLAN REVIEW
 PERMIT: 11080463
 ADD: 1500 N FLORIDA MANGO SUITE142
 CONT: MALASKY HOMES, INC.
 TEL: (561)471-8600
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 PERMIT: 11040647 1500 N FLORIDA MANGO SUITE 1,2 8B & 9B
 (FILE NET)
 INTERIOR DEMO OF WALLS, RAISE CEILING, NEW HVAC
 RE-PLUMB KITCHEN & ELECTRICAL OUTLETS.
 TYPE II-B
 SPRINKLERED
  
 SHEET A-1 LIFE SAFETY PLAN.
  
  
  
  
 1) 413.1 GENERAL. HIGH-PILED STOCK OR RACK STORAGE IN
 ANY OCCUPANCY GROUP SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 2) F] 903.2.6.1 HIGH-PILED STORAGE. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE IN ALL BUILDINGS OF
 GROUP M WHERE STORAGE OF MERCHANDISE IS IN HIGH-PILED
 OR RACK STORAGE ARRAYS.
  
 3) 2208.1 STORAGE RACKS. THE DESIGN, TESTING AND
 UTILIZATION OF INDUSTRIAL STEEL STORAGE RACKS SHALL BE
 IN ACCORDANCE WITH THE RMI SPECIFICATION FOR THE
 DESIGN, TESTING AND UTILIZATION OF INDUSTRIAL STEEL
 STORAGE RACKS. RACKS IN THE SCOPE OF THIS SPECIFICATION
 INCLUDE INDUSTRIAL PALLET RACKS, MOVABLE SHELF RACKS
 AND STACKER RACKS, AND DOES NOT APPLY TO OTHER TYPES OF
 RACKS, SUCH AS DRIVE-IN AND DRIVE-THROUGH RACKS,
 CANTILEVER RACKS, PORTABLE RACKS OR RACK BUILDINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]