| Plan Review Notes For Permit 11080459 |
| Permit Number |
11080459 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-12 15:37:51 | ELECTRIC PERMIT AND PLANS REQUIRED FOR THIS REMODEL. | | | SHOW EXISTING SERVICE SIZE AND LOCATION NEC 215.5 | | | PROVIDE SMOKE DETECTORS AS REQUIRED BY CODE. FBC | | | 704.4.3 | | | PROVIDE GFCI PROTECTION AS NEEDED. NEC 210.8 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|