Plan Review Notes
Plan Review Notes For Permit 11080458
Permit Number 11080458
Review Stop B
Sequence Number 2
Notes
Date Text
2011-10-12 07:57:55BUILDING PLAN REVIEW
 PERMIT: 11080458
 ADD: 426 9TH ST/ FRONT BUILDING
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1)COMPLIED.
  
 2) PARTIALLY COMPLIED.THE FIRST AND SECOND FLOOR DO NOT
 INDICATE ANY FIRE RATED CORRIDORS, ANY RATED ENTRANCE
 DOORS FOR DWELLING UNITS OR SLEEPING UNITS NOR RATED
 SEPARATION WALLS BETWEEN DWELLING UNITS.
 2007 /09 FBC-B 438.2 SEPARATION WALLS. PLANS INDICATE
 TENANT SEPERATION WALLS ONLY PARTIALLY RATED AROUND THE
 STAIRWELL, BOTH THE FIRST FLOOR AND SECOND FLOOR.
 2007 / 09 FBC-B TABLE 715.4
  
 3B) 12.3 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO
 OR THROUGH FIRE WALLS, FIRE-BARRIER WALLS,
 SMOKE-BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY
 WITH SECTIONS 712.3.1 THROUGH 712.3.4
  
 4) PARTIALLY APPROVED. THE NEW CONFIGURATION FOR THE
 INTERIOR STAIRS INDICATES STAIR RISERS AND TREADS
 DIRECTLY IN FRONT OF THE SECOND STORY UNIT ENTRANCES.
 PLEASE REVIEW!!!
 STAIRS 2007/ 09 EXST BLDG CODE 703.2.1 ALL EXISTING
 INTERIOR VERTICAL OPENINGS CONNECTING TWO OR MORE
 FLOORS SHALL COMPLY WITH THE APPROPRIATE SECTIONS OF
 THE FLORIDA FIRE PREVENTION CODE.
  
 5-9) COMPLIED.
  
 10) PARTIALLY COMPLIED, PLEASE REVIEW 2ND FLOOR ENTRY
 DOORS. ENTRY DOORS TO UNITS WILL NEED TO SHOW
 COMPLIANCE WITH: 2007/ 09 FBC-B 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). WHERE
 THIS SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32
 INCHES. EXCEPTIONS: 1. THE MINIMUM AND MAXIMUM WIDTH
 SHALL NOT APPLY TO DOOR OPENINGS THAT ARE NOT PART OF
 THE REQUIRED MEANS OF EGRESS IN GROUP R-2 AND R-3
 OCCUPANCIES.
  
 11-12) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  