| 2011-10-12 07:57:55 | BUILDING PLAN REVIEW |
| | PERMIT: 11080458 |
| | ADD: 426 9TH ST/ FRONT BUILDING |
| | CONT: RECORD CONSTRUCTION |
| | TEL: (561)662-2775 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II |
| | 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1)COMPLIED. |
| | |
| | 2) PARTIALLY COMPLIED.THE FIRST AND SECOND FLOOR DO NOT |
| | INDICATE ANY FIRE RATED CORRIDORS, ANY RATED ENTRANCE |
| | DOORS FOR DWELLING UNITS OR SLEEPING UNITS NOR RATED |
| | SEPARATION WALLS BETWEEN DWELLING UNITS. |
| | 2007 /09 FBC-B 438.2 SEPARATION WALLS. PLANS INDICATE |
| | TENANT SEPERATION WALLS ONLY PARTIALLY RATED AROUND THE |
| | STAIRWELL, BOTH THE FIRST FLOOR AND SECOND FLOOR. |
| | 2007 / 09 FBC-B TABLE 715.4 |
| | |
| | 3B) 12.3 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO |
| | OR THROUGH FIRE WALLS, FIRE-BARRIER WALLS, |
| | SMOKE-BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY |
| | WITH SECTIONS 712.3.1 THROUGH 712.3.4 |
| | |
| | 4) PARTIALLY APPROVED. THE NEW CONFIGURATION FOR THE |
| | INTERIOR STAIRS INDICATES STAIR RISERS AND TREADS |
| | DIRECTLY IN FRONT OF THE SECOND STORY UNIT ENTRANCES. |
| | PLEASE REVIEW!!! |
| | STAIRS 2007/ 09 EXST BLDG CODE 703.2.1 ALL EXISTING |
| | INTERIOR VERTICAL OPENINGS CONNECTING TWO OR MORE |
| | FLOORS SHALL COMPLY WITH THE APPROPRIATE SECTIONS OF |
| | THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 5-9) COMPLIED. |
| | |
| | 10) PARTIALLY COMPLIED, PLEASE REVIEW 2ND FLOOR ENTRY |
| | DOORS. ENTRY DOORS TO UNITS WILL NEED TO SHOW |
| | COMPLIANCE WITH: 2007/ 09 FBC-B 1008.1.1 SIZE OF DOORS. |
| | THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE |
| | SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL |
| | PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES (813 |
| | MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS |
| | SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE |
| | STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). WHERE |
| | THIS SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32 |
| | INCHES. EXCEPTIONS: 1. THE MINIMUM AND MAXIMUM WIDTH |
| | SHALL NOT APPLY TO DOOR OPENINGS THAT ARE NOT PART OF |
| | THE REQUIRED MEANS OF EGRESS IN GROUP R-2 AND R-3 |
| | OCCUPANCIES. |
| | |
| | 11-12) COMPLIED. |
| | |