Plan Review Notes
Plan Review Notes For Permit 11080458
Permit Number 11080458
Review Stop P
Sequence Number 1
Notes
Date Text
2011-08-25 12:16:04FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET #1 THE MINIMUM WIDTH OF THE NEW FRAMED
 BATHROOM WOULD BE 7'-6" - USING A STANDARD 30" WIDE
 TUB.
 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS.
 A WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO
 ANY SIDE WALL, PARTITION, VANITY OR OTHER OBSTRUCTION,
 OR CLOSER THAN 30 INCHES (762 MM) CENTER-TO-CENTER
 BETWEEN ADJACENT FIXTURES. THERE SHALL BE AT LEAST A
 21-INCH (533 MM) CLEARANCE IN FRONT OF THE WATER
 CLOSET, URINAL, LAVATORY OR BIDET TO ANY WALL, FIXTURE
 OR DOOR. WATER CLOSET COMPARTMENTS SHALL NOT BE LESS
 THAN 30 INCHES (762 MM) WIDE AND 60 INCHES
  
 2. SHEET #2 THE CENTRAL WASHING FACILITY REQUIRES A 3"
 FLOOR DRAIN. PLUMBING 412.4
  
 3. ON THE PLUMBING RISER A VENT OR WET VENT IS REQUIRED
 BETWEEN THE WC AND TUB. PLUMBING 901.2.1
  
 4. ON THE RISER 2ND FLOOR - THE KITCHEN SINK IS NOT
 PERMITTED ON THE VERTICAL WET VENT AND THE LAV WOULD BE
 ABOVE THE WC AND TUB.
 PLUMBING 909.1.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  