| Plan Review Notes For Permit 11080458 |
| Permit Number |
11080458 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-25 12:16:04 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET #1 THE MINIMUM WIDTH OF THE NEW FRAMED | | | BATHROOM WOULD BE 7'-6" - USING A STANDARD 30" WIDE | | | TUB. | | | 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS. | | | A WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE | | | SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO | | | ANY SIDE WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, | | | OR CLOSER THAN 30 INCHES (762 MM) CENTER-TO-CENTER | | | BETWEEN ADJACENT FIXTURES. THERE SHALL BE AT LEAST A | | | 21-INCH (533 MM) CLEARANCE IN FRONT OF THE WATER | | | CLOSET, URINAL, LAVATORY OR BIDET TO ANY WALL, FIXTURE | | | OR DOOR. WATER CLOSET COMPARTMENTS SHALL NOT BE LESS | | | THAN 30 INCHES (762 MM) WIDE AND 60 INCHES | | | | | | 2. SHEET #2 THE CENTRAL WASHING FACILITY REQUIRES A 3" | | | FLOOR DRAIN. PLUMBING 412.4 | | | | | | 3. ON THE PLUMBING RISER A VENT OR WET VENT IS REQUIRED | | | BETWEEN THE WC AND TUB. PLUMBING 901.2.1 | | | | | | 4. ON THE RISER 2ND FLOOR - THE KITCHEN SINK IS NOT | | | PERMITTED ON THE VERTICAL WET VENT AND THE LAV WOULD BE | | | ABOVE THE WC AND TUB. | | | PLUMBING 909.1.1 | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|