Plan Review Notes
Plan Review Notes For Permit 11080456
Permit Number 11080456
Review Stop B
Sequence Number 2
Notes
Date Text
2011-10-11 16:42:31BUILDING PLAN REVIEW
 PERMIT: 11080456
 ADD: 440 9TH ST/ BACK BUILDING
 CONT: RECORD CONSTRUCTION
 TEL: (561)662-2775
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 OCT. 11/ 2011
 ACTION: DENIED
  
 1) COMPLIED.
  
  
 2) FROM 04/04/2001 THERE IS A 4 TIMES FEE HOLD FOR
 WORKING WITHOUT A PERMIT FOR PLUMBING, ELECTRICAL &
 BUILDING.
  
 3) COMPLIED, ONE SINGLE TENANT.
  
 4A) NOTE, THE INTERIOR STAIR HAS BEEN FILED IN AND A
 ROOM ( DEN) HAS BEEN CREATED. PLANS DO NOT INDICATE
 SIZE OR SPACING OF NEW FRAMING MEMBERS NOR FINISHES
 REQUIRED FOR HORIZONTAL TENANT SEPERATION FBC-B 438.3.
  
 4B) THE EXTERIOR STAIR IS THE ONLY MEANS OF EGRESS , A
 PERSON ENTER THE 2ND FLOOR FROM THE EXTERIOR STAIR
 LANDING INTO BEDROOM # 3. FBC-B 1014.1 EGRESS CAN'T BE
 THROUGH LOCKABLE ROOMS.
  
 COMMENT FROM 1ST REVIEW. STAIRS 2007/ 09 EXST BLDG CODE
 703.2.1 ALL EXISTING INTERIOR VERTICAL OPENINGS
 CONNECTING TWO OR MORE FLOORS SHALL COMPLY WITH THE
 APPROPRIATE SECTIONS OF THE FLORIDA FIRE PREVENTION
 CODE.
  
 5-12) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  