2011-08-24 13:19:10BUILDING PLAN REVIEW
 PERMIT: 11080456
 ADD: 440 9TH ST/ BACK BUILDING
 CONT: HURRICANE BUILDERS INC.
 TEL: (561)718-8678
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) HURRICANE BUILDERS INC. RR-0067321 IS A REGISTERED
 RESIDENTIAL CONTRACTOR, BY FLORIDA STATUTE 489.105(3) (
 C ) DEFINITIONS: ?RESIDENTIAL CONTRACTOR? MEANS A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO CONSTRUCTION,
 REMODELING, REPAIR, OR IMPROVEMENT OF ONE-FAMILY,
 TWO-FAMILY, OR THREE-FAMILY RESIDENCES NOT EXCEEDING
 TWO HABITABLE STORIES ABOVE NO MORE THAN ONE
 UNINHABITABLE STORY AND ACCESSORY USE STRUCTURES IN
 CONNECTION THEREWITH. THIS PERMIT CAN NOT BE ISSUED TO
 A RESIDENTIAL CONTRACTOR, IT WOULD BE CONSIDERED
 WORKING BEYOND THE SCOPE OF THEIR LICENSE.
  
 THE SECOND FLOOR LAYOUT IS NOT CLEAR AS TO THE ENTENT,
 IF THE SECOND FLOOR IS A SINGLE TENANT OR IF THIS IS
 (4) SEPERATE SLEEPING ROOMS WITH COMMON LIVING
 FACILITIES?
  
 2) FROM 04/04/2001 THERE IS A 4 TIMES FEE HOLD FOR
 WORKING WITHOUT A PERMIT FOR PLUMBING, ELECTRICAL &
 BUILDING.
  
 3) THE FIRST AND SECOND FLOOR DO NOT INDICATE ANY FIRE
 RATED CORRIDORS, ANY RATED ENTRANCE DOORS FOR DWELLING
 UNITS OR SLEEPING UNITS NOR RATED SEPARATION WALLS
 BETWEEN DWELLING UNITS.
 2007 /09 FBC-B 438.2 SEPARATION WALLS
 2007 / 09 EXST BLDG CODE 705.5 SEE 2009 SUPPLEMENTS
 COMPLY WITH SECTIONS;
 705.5.1.1- 705.5.4
 2007 / 09 FBC-B TABLE 715.4
  
 3B) 12.3 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO
 OR THROUGH FIRE WALLS, FIRE-BARRIER WALLS,
 SMOKE-BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY
 WITH SECTIONS 712.3.1 THROUGH 712.3.4
  
 4) STAIRS 2007/ 09 EXST BLDG CODE 703.2.1 ALL EXISTING
 INTERIOR VERTICAL OPENINGS CONNECTING TWO OR MORE
 FLOORS SHALL COMPLY WITH THE APPROPRIATE SECTIONS OF
 THE FLORIDA FIRE PREVENTION CODE.
  
 5) PLEASE PROVIDE COMPLIANCE WITH 2007/09 FBC 438.3
 HORIZONTAL SEPARATION. FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING SLEEPING UNITS IN
 THE SAME BUILDING SHALL BE CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711. PROVIDE UL OR OTHER FIRE RATING
 ASSEMBLY.
  
 5A) 711.3 FIRE-RESISTANCE RATING. THE FIRE-RESISTANCE
 RATING OF FLOOR AND ROOF ASSEMBLIES SHALL NOT BE LESS
 THAN THAT REQUIRED BY THE BUILDING TYPE OF
 CONSTRUCTION.. FLOOR ASSEMBLIES SEPARATING DWELLING
 UNITS IN THE SAME BUILDING OR SLEEPING UNITS IN
 OCCUPANCIES IN GROUP R-1, HOTEL OCCUPANCIES, R-2 AND
 I-1; AND FLOOR ASSEMBLIES SEPARATING INDIVIDUAL TENANT
 SPACES IN THE SAME BUILDING IN ALL OTHER OCCUPANCIES
 SHALL BE A MINIMUM OF 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION.
  
 5B) 2007 / 09 FBC-B 712.4.1 FIRE-RESISTANCE RATED
 ASSEMBLIES. PENETRATIONS OF THE FIRE-RESISTANCE RATED
 FLOOR, FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE
 OF A ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 712.4.1.1 THROUGH 712.4.1.4.
  
 6) 2007 / 09 EXST BLDG CODE (LEVEL III ALT) 804.1
 AUTOMATIC SPRINKLER SYSTEMS. AUTOMATIC SPRINKLER
 SYSTEMS SHALL BE PROVIDED IN ALL WORK AREAS IN
 ACCORDANCE WITH THE
 2007 / 09 FLORIDA BUILDING CODE, BUILDING 903.2.7 GROUP
 R. AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.3 SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS WITH A GROUP R FIRE AREA. NOTE
 DEPENDING ON THE RESPONCE TO COMMENT # 1 THIS MAY BE
 CONSIDERED A 1 / 2 FAMILY DWELLING UNIT AND NOT FALL
 UNDER THIS CODE SECTION.
  
 7) PROVIDE COMPLIANCE WITH 2007/ 09 FBC-B 803.5
 INTERIOR FINISH REQUIREMENTS BASED ON GROUP. INTERIOR
 WALL AND CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX
 NOT GREATER THAN THAT SPECIFIED IN TABLE 803.5 FOR THE
 GROUP AND LOCATION DESIGNATED.
  
 8) PROVIDE COMPLIANCE WITH 2007/09 FBC-B 1207.2
 AIR-BORNE SOUND. WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 9) PROVIDE COMPLIANCE WITH 2007 / 09 FBC-B 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 10) ENTRY DOORS TO UNITS WILL NEED TO SHOW COMPLIANCE
 WITH: 2007/ 09 FBC-B 1008.1.1 SIZE OF DOORS. THE
 MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT
 FOR THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR
 WIDTH OF NOT LESS THAN 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). WHERE THIS
 SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32 INCHES.
 EXCEPTIONS: 1. THE MINIMUM AND MAXIMUM WIDTH SHALL NOT
 APPLY TO DOOR OPENINGS THAT ARE NOT PART OF THE
 REQUIRED MEANS OF EGRESS IN GROUP R-2 AND R-3
 OCCUPANCIES.
  
 11A) 2007 / 09 EXST BLDG CODE 804.2 FIRE ALARM AND
 DETECTION SYSTEMS. FIRE ALARM AND DETECTION SYSTEMS
 SHALL COMPLY WITH THE APPROPRIATE SECTIONS OF THE
 FLORIDA FIRE PREVENTION CODE .
  
 11B)EXST BLDG CODE 804.2.1 MANUAL FIRE ALARM SYSTEMS.
 WHERE REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING ,
 A MANUAL FIRE ALARM SYSTEM SHALL BE PROVIDED THROUGHOUT
 THE WORK AREA. ALARM NOTIFICATION APPLIANCES SHALL BE
 PROVIDED ON SUCH FLOORS AND SHALL BE AUTOMATICALLY
 ACTIVATED AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING.
 EXCEPTIONS:
 1. ALARM-INITIATING AND NOTIFICATION APPLIANCES SHALL
 NOT BE REQUIRED TO BE INSTALLED IN TENANT SPACES
 OUTSIDE OF THE WORK AREA.
 2. VISUAL ALARM NOTIFICATION APPLIANCES ARE NOT
 REQUIRED, EXCEPT WHERE AN EXISTING ALARM SYSTEM IS
 UPGRADED OR REPLACED OR WHERE A NEW FIRE ALARM SYSTEM
 IS INSTALLED.
  
 11C) EXST BLDG CODE 804.2.2 AUTOMATIC FIRE DETECTION.
 WHERE REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING
 FOR NEW BUILDINGS, AUTOMATIC FIRE DETECTION SYSTEMS
 SHALL BE PROVIDED THROUGHOUT THE WORK AREA.
  
 11D) 2007 / 09 FBC-B
 [F] 907.2.10.1.2 GROUPS R-2, R-3, R-4 AND I-1. SINGLE-
 OR MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AND
 MAINTAINED IN GROUPS R-2, R-3, R-4 AND I-1, REGARDLESS
 OF OCCUPANT LOAD AT ALL OF THE FOLLOWING LOCATIONS:
  
 1. ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
  
 2. IN EACH ROOM USED FOR SLEEPING PURPOSES.
  
 3. IN EACH STORY WITHIN A DWELLING UNIT, INCLUDING
 BASEMENTS BUT NOT INCLUDING CRAWL SPACES AND
 UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS
 WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR
 BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON
 THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER
 LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE
 FULL STORY BELOW THE UPPER LEVEL.
  
 12)THIS COMMEENT MAY OR MAY NOT APPLY DEPENDING ON THE
 RESPONCE TO COMMENT # 1. PLEASE REVIEW THE REQUIREMENTS
 FOR AN EFFICIENCY DWELLING UNIT. 2007 / 09 FBC-B
 1208.4.
 EFFICIENCY DWELLING UNITS. AN EFFICIENCY LIVING UNIT
 SHALL CONFORM TO THE REQUIREMENTS OF THE CODE EXCEPT AS
 MODIFIED HEREIN:
  
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
  
 2. THE UNIT SHALL BE PROVIDED WITH A SEPARATE CLOSET.
  
 3. THE UNIT SHALL BE PROVIDED WITH A KITCHEN SINK,
 COOKING APPLIANCE AND REFRIGERATION FACILITIES, EACH
 HAVING A CLEAR WORKING SPACE OF NOT LESS THAN 30 INCHES
 (762 MM) IN FRONT. LIGHT AND VENTILATION CONFORMING TO
 THIS CODE SHALL BE PROVIDED.
  
 4. THE UNIT SHALL BE PROVIDED WITH A SEPARATE BATHROOM
 CONTAINING A WATER CLOSET, LAVATORY AND BATHTUB OR
 SHOWER.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO