| Plan Review Notes For Permit 11080455 |
| Permit Number |
11080455 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-25 13:26:22 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | | | | SHEET #1 SECOND FLOOR. | | | 1.THE MINIMUM BATHROOM WIDTH FOR A WC AND LAV WOULD BE | | | 60". | | | | | | 2. IN THE LARGE APARTMENT BATHROOM THE MINIMUM SIZE FOR | | | A SHOWER WOULD BE 30" X 30" (900 S.I.) OR 25" X 52" PER | | | EXCEPTION. | | | 417.4 SHOWER COMPARTMENTS. EXCEPTION: SHOWER | | | COMPARTMENTS HAVING NOT LESS THAN 25 INCHES (635 MM) IN | | | MINIMUM DIMENSION MEASURED FROM THE FINISHED INTERIOR | | | DIMENSION OF THE COMPARTMENT, PROVIDED THAT THE SHOWER | | | COMPARTMENT HAS A MINIMUM OF 1,300 SQUARE INCHES (.838 | | | M2) OF CROSS-SECTIONAL AREA. | | | 2B. THE LAV DOES NOT APPEAR TO BE 15" FROM THE WALL. | | | | | | SHEET #1 FIRST FLOOR. | | | 1. THE LAV DOES NOT APPEAR TO BE 15" FROM THE SIDE | | | WALL. | | | | | | SHEET #2 | | | 1. ON THE PLUMBING RISER A VENT OR WET VENT IS REQUIRED | | | BETWEEN THE WC AND TUB. PLUMBING 901.2.1 | | | | | | 2. ON THE RISER 2ND FLOOR - THE KITCHEN SINK IS NOT | | | PERMITTED ON THE VERTICAL WET VENT AND THE LAV WOULD BE | | | ABOVE THE WC AND TUB. | | | PLUMBING 909.1.1 | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|