2011-08-22 10:47:461 NORTH CLEMATIS STREET - SUITE #200
 PERMIT #11080435
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-1.0: IN ADDITION TO THE FIRE ALARM AND FIRE
 SPRINKLER, THE MAG LOCK DOORS SHALL UNLOCK UPON LOSS OF
 POWER CONTROLLING THE LOCKS OR LOCKING MECHANISM.
  
 SHEET LS-1.0: THE ELEVATOR LOBBY MAG LOCK SIGNAGE
 SHOULD READ PULL UNTIL ALARM SOUNDS - DOOR CAN BE
 OPENED IN 15 SECONDS. LETTERS SHALL BE AT LEAST 1-INCH
 IN HEIGHT AND 1/8-INCH STROKE. ONCE THE DOOR LOCK HAS
 BEEN RELEASED BY THE APPLICATION OF FORCE TO THE
 RELEASEING DEVICE, RELOCKING SHALL BE BY MANUAL MEANS
 ONLY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW