2011-08-18 14:26:103501 ELECTRONICS WAY
 PERMIT #11080358
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NFPA 13 SECTION 12.3.4.1.3 INDICATES AISLES SHALL BE
 SEPARATED BY AT LEAST FOUR FEET. THE PLANS ONLY SHOW
 THREE FEET BETWEEN AISLES.
  
 PROVIDE AN ELEVATION VIEW ON THE PLANS SIMILIAR TO NFPA
 13 FIGURE 12.3.4.4.1.3(B) SHOWING THE LOCATION OF THE
 RACK SPRINKLERS.
  
 PRESSURES AT THE 1-1/2" HOSE STATION OUTLETS SHALL BE
 LIMITED TO 100 PSI PER NFPA 13.
  
 PER FLORIDA FIRE PREVENTION CODE (NFPA 1) SECTION
 34.5.5, AUTOMATIC SPRINKLER SYSTEMS SHALL HAVE APPROVED
 CENTRAL STATION WATERFLOW ALARM SERVICE. ALARM SERVICE
 SHALL COMPLY WITH NFPA 72.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW