| Plan Review Notes For Permit 11080311 |
| Permit Number |
11080311 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-19 14:49:29 | 2004 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE SIGNATURE OF THE QUALIFIER THAT HOLDS THE | | | MECHANICAL CONTRACTOR LICENSE IS REQUIRED ON THE | | | REVISED MECHANICAL PLANS. FS 471.003 (2) (H) | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE REVISED PLANS. | | | | | | 3) THE REVISED PLANS APPEAR TO SHOW AN AIR HANDLER FOR | | | THE FIRST FLOOR AND ANOTHER ON FOR THE SECOND FLOOR. | | | THE APPROVED PLANS HAVE ONE 60,000 BTU AIR HANDLER. | | | PLEASE CLARIFY. IF THERE ARE TWO SEPARATE SYSTEMS, THE | | | LOCATION OF THE ADDITIONAL CONDENSING UNIT WILL NEED TO | | | BE SHOWN ON THE DRAWINGS AND APPROVED BY ZONING. | | | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR FROM ALL HABITABLE ROOMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|