Plan Review Notes
Plan Review Notes For Permit 11080246
Permit Number 11080246
Review Stop E
Sequence Number 1
Notes
Date Text
2011-08-15 14:16:08 
 PLEASE PROVIDE DETAILED ELECTRICAL PLAN FOR ALL
 IMPROVEMENTS SHOWING EXISTING AND NEW WORK.
  
 INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING
 SERVICE, MAIN DISCONNECT AND PANELBOARD. NEC 215.5
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
 ADDITIONAL RECEPTACLES REQUIRED IN THE BEDROOMS AND
 HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE
 THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE
 THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND A SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT EACH
 ENTRANCE. NEC 210.52
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  