| Plan Review Notes For Permit 11080175 |
| Permit Number |
11080175 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-11 12:16:22 | 400 NORTH FLAGLER DRIVE | | | PERMIT #11080175 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | VERIFY EXIT "LITE" IS A COMBINATION EXIT SIGN WITH | | | EMERGENCY LIGHT. | | | | | | SLIDING DOORS ARE NOT PERMITTED TO BE USED AS AN EXIT. | | | REMOVE EXIT SIGN. | | | | | | PROVIDE TACTILE SIGNAGE AT REQUIRED EXIT DOOR WITH EXIT | | | SIGN. | | | | | | ONLY PROVIDE DOOR LEVER ON ACTIVE DOOR LEAF SO | | | OPERATIONAL DOOR IS READILY APPARENT. | | | | | | AN EXISTING FIRE ALARM STROBE DEVICE IS SHOWN IN THE | | | FITNESS ROOM; THIS DEVICE WOULD HAVE PREVIOUSLY BEEN | | | LOCATED IN THE LOBBY. ANOTHER NOTIFICATION APPLIANCE IS | | | MOST LIKELY NEEDED IN THE LOBBY. | | | | | | INDICATE THE FIRE SPRINKLER LOCATIONS ON THE SPACE | | | ADJACENT TO THE NEW FITNESS ROOM SO IT CAN BE | | | DETERMINED IF PROPER COVERAGE EXISTS OUTSIDE THE | | | FITNESS ROOM. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|