| Plan Review Notes For Permit 11080145 |
| Permit Number |
11080145 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-10 14:37:17 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE PROVIDE MORE INFORMATION REGARDING OCCUPANCY | | | CLASSIFICATION OF THIS STRUCTURE. OUR RECORDS (PRIOR TO | | | SUBMITTAL OF A RES REMOD PERMIT SHOWING RENOVATION TO | | | EXISTING DWELLING UNIT) SHOW THIS AS BUSINESS | | | OCCUPANCY. | | | | | | 2. UNLESS EVIDENCE CAN BE PROVIDED THAT THIS WAS A | | | MIXED USE STRUCTURE, SHOW COMPLIANCE WITH FBC11-4.13.8 | | | (DOOR THRESHOLD HEIGHT LIMITATION). | | | | | | 3. FAC9N-3, PROVIDE FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL FOR THE DOOR. THE EVALUATION REPORT WAS | | | SUBMITTED BUT THE COVER SHEET FROM | | | WWW.FLORIDABUILDING.ORG IS ALSO REQUIRED. | | | | | | 4. IMPACT PROTECTION REQUIRED, FBC1609.1.4. NON IMPACT | | | STOREFRONT PRODUCT APPROVALS WERE SUBMITTED. | | | | | | 5. THE FLOOR PLAN SHOWS HORIZONTAL ROLLER WINDOWS, BUT | | | BOTH HORIZONTAL ROLLER AND SINGLE HUNG WINDOW PRODUCT | | | APPROVALS WERE SUBMITTED. | | | | | | |
|