 PERMIT #11080144
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS ON THE PLANS SHOULD BE CORRECTED TO READ
 2421 OKEECHOBEE BOULEVARD.
  
 DOOR #1: FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. AS A SUBSTITUTION FOR PANIC HARDWARE,
 THE MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR
 KEYED DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE
 SIGN STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST
 1-INCH IN HEIGHT. A THUMB TURN STYLE LOCK IS NOT
 PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  