| Plan Review Notes For Permit 11080144 |
| Permit Number |
11080144 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-17 14:56:00 | BUILDING PLAN REVIEW | | | PERMIT: 11080144 | | | ADD: 2421 OKEECHOBEE BLVD | | | CONT: TBD | | | TEL: (772)486-4190 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) DISCREPANCY IN WIND DESIN PRESSURES PLEASE REVIEW | | | SHEET A2.0 INDICATE A "B" EXPOSURE WHILE S0.2 INDICATES | | | A "C" EXPOSURE. THE JOBSITE IS LOCATED IN A "C" | | | EXPOSURE WITH HIGHER DESIGN PRESSURES THAN SHOWN ON | | | A2.0. 2007/09 FBC-B 1609. | | | | | | 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING | | | REPORTS ARE AS FOLLOWS: | | | A) STOREFRONT GLAZED WALL SYSTEM | | | B) STOREFRONT EXTERIOR DOOR | | | C) FIXED GLASS SYSTEM | | | D) SERVICE WINDOW | | | E) ROOFING ASSEMBLIES | | | | | | 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|