Plan Review Notes
Plan Review Notes For Permit 11080127
Permit Number 11080127
Review Stop Z
Sequence Number 1
Notes
Date Text
2011-08-10 10:06:38ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.10.2011
 PERMIT NO.: 11080127
 ADDRESS: 3401 PARKER AVENUE
 CONTRACTOR/CONTACT: JAMES FAZZINI
 TELEPHONE NO.: 954.325.2133
 SCOPE OF REVIEW: INSTALLATION OF UNDERGROUND ELECTRICAL
 CONDUIT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO ORDINANCE NO. 4114-08, REGULATING THE
 PBAU ATHLETIC COMPLEX COMMUNITY SERVICE PLANNED
 DEVELOPMENT (CSPD), DIRECT OR INDIRECT LIGHTING SHALL
 NOT EXCEED 0.5 FOOTCANDLES WHEN MEASURE FROM A
 RESIDENTIAL ZONING DISTRICT. A PHOTOMETRIC PLAN SHALL
 BE PROVIDED INDICATING THE FOOTCANDLES AT THE PROPERTY
 LINES.
  
 2. AS DISCUSSED IN NUMEROUS CONSTRUCTION PROGRESS
 MEETINGS, MODIFICATIONS TO THE PARKING LOT
 CONFIGURATION, ETC. ARE NEEDED DUE TO THE LOCATION OF
 SOME OF THE UNDERGROUND UTILITIES, FIRE HYDRANTS, ETC.
 AN AMENDMENT TO THE CSPD SHALL BE SUBMITTED, AND
 APPROVED BY, THE PLANNING AND ZONING DEPARTMENT PRIOR
 TO THE ISSUANCE OF THE BUILDING PERMIT AS THE PARKING
 LOT MODIFICATIONS WILL LIKELY ALTER THE CONFIGURATION
 OF THE SITE LIGHTING.
  
 3. PURSUANT TO ORDINANCE NO. 4114-08, PEDESTRIAN-SCALE
 LIGHTING IS TO BE PROVIDED THROUGH-OUT THE CITY?S PARK,
 AT THE EXPENSE OF THE DEVELOPER. THE DESIGN AND
 LOCATION OF THE LIGHTING SHALL BE REVIEWED AND APPROVED
 BY THE CITY?S DIRECTOR OF PARKS AND RECREATION, AND
 ENGINEERING SERVICES DEPARTMENT, PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
  
 4. PURSUANT TO ORDINANCE NO. 4114-08, THE DEVELOPER
 SHALL PROVIDE WRITTEN EVIDENCE THAT THE FEDERAL
 AVIATION ADMINISTRATION (FAA) HAS REVIEWED AND APPROVED
 THE HEIGHT OF ALL PROPOSED STRUCTURES (INCLUDING
 LIGHTING) AS WELL AS THE LIGHTING PLAN TO ENSURE THAT
 SUCH LIGHTING WILL NOT INTERFERE WITH AIR NAVIGATION.
  
 5. PLEASE NOTE THAT A DETAIL/ELEVATION WILL NEED TO BE
 PROVIDED FOR THE FIXTURES PROPOSED AT THE SPORTS
 FIELDS. THIS COMMENT DOES NOT PERTAIN TO THE
 UNDERGROUND CONDUIT, BUT WILL NEED TO BE ADDRESSED
 PRIOR TO THE ISSUANCE OF A PERMIT FOR THE ABOVE-GROUND
 INSTALLATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved