| Plan Review Notes For Permit 11080126 |
| Permit Number |
11080126 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-25 15:09:14 | 5400 GEORGIA AVENUE | | | PERMIT #11080126 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | OUTDOOR STORAGE OF CORROSIVE LIQUIDS SHALL NOT BE | | | LOCATED WITHIN 20 FEET OF PROPERTY LINES PER SECTION | | | 64.2.1 OF NFPA 1 - FLORIDA EDITION. | | | | | | NOTE 1: PER CHAPTER 64 (FFPC) THE STORAGE AMOUNT OF | | | CORROSIVE LIQUIDS CAN EXCEED 1950 GALLONS PER OUTDOOR | | | CONTROL AREA AS DETERMINED BY TABLE 60.2.6.5 OF NFPA 1 | | | - FLORIDA EDITION. | | | | | | NOTE 2: THIS IS NOT AN OXIDIZER PER NFPA 430 (12 % | | | NAOCL - SODIUM HYPOCHLORITE). THIS IS A CORROSIVE | | | CHEMICAL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | |
|