2011-08-25 15:09:145400 GEORGIA AVENUE
 PERMIT #11080126
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OUTDOOR STORAGE OF CORROSIVE LIQUIDS SHALL NOT BE
 LOCATED WITHIN 20 FEET OF PROPERTY LINES PER SECTION
 64.2.1 OF NFPA 1 - FLORIDA EDITION.
  
 NOTE 1: PER CHAPTER 64 (FFPC) THE STORAGE AMOUNT OF
 CORROSIVE LIQUIDS CAN EXCEED 1950 GALLONS PER OUTDOOR
 CONTROL AREA AS DETERMINED BY TABLE 60.2.6.5 OF NFPA 1
 - FLORIDA EDITION.
  
 NOTE 2: THIS IS NOT AN OXIDIZER PER NFPA 430 (12 %
 NAOCL - SODIUM HYPOCHLORITE). THIS IS A CORROSIVE
 CHEMICAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  