2011-09-08 13:40:533990 NORTH FLAGLER DRIVE - MAINTENANCE BUILDING
 PERMIT #11080117
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: CIVIL SITE DRAWINGS WILL BE SUBMITTED AS SEPARATE
 PACKAGE.
  
 *****PROVISO*****
  
 IDLE PALLETS SHALL BE STORED OUTSIDE OR IN A SEPARATE
 BUILDING DESIGNED FOR PALLET STORAGE. INDOOR STORAGE OF
 PALLETS IS PERMITTED IF THE BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. OUTDOOR PALLETS SHALL BE
 LOCATED AT LEAST 20 FEET FROM BUILDINGS.
  
 STORAGE MORE THAN 12 FEET IN HEIGHT OR STORAGE LOCATED
 WITHIN THE ATTIC SPACE REQUIRES THE BUILDING TO BE
 PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW