| 2011-08-12 13:23:35 | 3990 NORTH FLAGLER DRIVE - MAINTENANCE BUILDING |
| | PERMIT #11080117 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: CIVIL SITE DRAWINGS WILL BE SUBMITTED AS SEPARATE |
| | PACKAGE. |
| | |
| | *****PROVISO***** |
| | |
| | NO ADDRESS PROVIDED IN TITLEBLOCK. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER |
| | FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| | 69A-60.0081. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| | EDITION 2007. |
| | |
| | PROVIDE EQUIPMENT AND STORAGE LAYOUT PLAN. INDICATE |
| | WHAT MATERIALS WILL BE STORED, THE APPROXIMATE |
| | QUANTITIES AND HOW THE MATERIALS WILL BE STORED (PILED, |
| | RACK, PALLET ETC.). INDICATE IF ANY FLAMMABLE OR |
| | COMBUSTIBLE LIQUIDS OR GASES WILL BE STORED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |