2011-08-30 16:53:58PER DOUG, BY-PASS AND ASSIGN NEW STOP AFTER ISSUEING
 STRUCTURE ONLY.
2011-08-23 11:29:14NEW MAINTENANCE BUILDING #11080117
 3990 N. FLAGLER DR.
  
 GENERAL PURPOSE RECEPTACLES LOCATED OUTDOORS, IN
 BATHROOMS AND ALL MAINTENANCE AREAS REQUIRE GFCI
 PROTECTION. NEC 210.8
 PLEASE PROVIDE THE FEEDER SIZES FOR PANEL BOARDS MC AND
 MD. INDICATE ON THE SITE ELECTRICAL PLAN WHERE PANEL
 BOARDS MC AND MD ARE LOCATED. NEC 215.5
 FEEDER TO TRANSFORMER MB IS APPEARS TO BE UNDERSIZED.
 NEC T. 310.16
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]