| Plan Review Notes For Permit 11080117 |
| Permit Number |
11080117 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-30 16:53:58 | PER DOUG, BY-PASS AND ASSIGN NEW STOP AFTER ISSUEING | | | STRUCTURE ONLY. | | 2011-08-23 11:29:14 | NEW MAINTENANCE BUILDING #11080117 | | | 3990 N. FLAGLER DR. | | | | | | GENERAL PURPOSE RECEPTACLES LOCATED OUTDOORS, IN | | | BATHROOMS AND ALL MAINTENANCE AREAS REQUIRE GFCI | | | PROTECTION. NEC 210.8 | | | PLEASE PROVIDE THE FEEDER SIZES FOR PANEL BOARDS MC AND | | | MD. INDICATE ON THE SITE ELECTRICAL PLAN WHERE PANEL | | | BOARDS MC AND MD ARE LOCATED. NEC 215.5 | | | FEEDER TO TRANSFORMER MB IS APPEARS TO BE UNDERSIZED. | | | NEC T. 310.16 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|