| 2011-08-12 12:24:42 | 4050 NORTH FLAGLER DRIVE - CAFETERIA BUILDING |
| | PERMIT #11080115 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: CIVIL PLANS ARE BEING SUBMITTED IN A SEPARATE |
| | PACKAGE. |
| | |
| | *****PROVISO***** |
| | |
| | NO ADDRESS PROVIDED IN TITLEBLOCK. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER |
| | FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| | 69A-60.0081. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | NO SEATING OR FURNITURE PLAN SUBMITTED. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET A101: NO PORTABLE FIRE EXTINGUISHER PROVIDED FOR |
| | OUTDOOR BAR AREA. THE TRAVEL DISTANCE TO EXTINGUISHERS |
| | SHALL NOT EXCEED 75 FEET. EXTINGUISHERS SHALL HAVE A |
| | MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A |
| | LICENSED FIRE EXTINGUISHER COMPANY. |
| | |
| | SHEET A101: PANIC HARDWARE MENTIONED ON LIFE SAFETY |
| | PLAN, BUT NO PANIC HARDWARE INDICATED ON DOOR SCHEDULE |
| | FOR DOORS 104A, 104B AND 104C. |
| | |
| | SHEET A104: VERIFY DEEP FAT FRYERS EQUIPPED WITH A |
| | SEPARATE HIGH-LIMIT CONTROL IN ADDITION TO THE |
| | ADJUSTABLE THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN |
| | THE FAT TEMPERATURE REACHES 475F DEGREES AT 1 INCH |
| | BELOW THE SURFACE. |
| | |
| | SHEET A502/A504: ALL INTERIOR WALL AND CEILING FINISHES |
| | SHALL BE CLASS A, CLASS B OR CLASS C. |
| | |
| | SHEET E-3: EXIT SIGNAGE FROM THE DINING AREA SHALL NOT |
| | ROUTE OCCUPANTS TO EXIT THROUGH THE KITCHEN. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |