| 2011-08-22 14:26:06 | CAFETERIA BUILDING # 11080115 | | | | | | GENERAL PURPOSE RECEPTACLES LOCATED AT THE BAR, | | | KITCHEN, OUTDOOR AND BATHROOMS REQUIRE GFCI PROTECTION. | | | NEC 210.8 | | | VERIFY THE OUTDOOR FANS ARE RATED FOR A WET OR DAMP | | | LOCATION. NEC 110.11 | | | PANELBOARD CB AND CC REQUIRE OVERCURRENT PROTECTION. | | | NEC 408.36 | | | DRY-TYPE TRANSFORMERS OVER 112 1/2 KVA REQUIRE A | | | TRANSFORMER ROOM OF FIRE RESISTANT CONSTRUCTION OR MUST | | | BE CONSTRUCTED WITH INSULATION SYSTEM CLASS 155 OR | | | HIGHER AND COMPLETELY ENCLOSED OR SEPARATED FROM | | | COMBUSTIBLES. | | | PROVIDE SAFETY CLEARANCES OF 42 INCHES FROM THE 150K | | | TRANSFORMER TO PANEL BOARD CB. IF THE TRANSFORMER IS TO | | | BE WALL OR CEILING MOUNTED PLEASE PROVIDE AN ENGINEERED | | | MOUNTING DETAIL. NEC TABLE 110.26, 110.13 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|