| 2011-08-10 09:13:58 | 2471 OKEECHOBEE BOULEVARD - SUITE HM |
| | PERMIT #11080112 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: THIS PERMIT IS FOR PREPARATION OF SHELL SPACE |
| | ONLY. SEPARATE PLANS AND PERMIT ARE NEEDED FOR THE |
| | TENANT BEFORE OCCUPANCY WILL BE ALLOWED. |
| | |
| | |
| | *****PROVISO***** |
| | |
| | NO ADDRESS PROVIDED IN TITLEBLOCK. |
| | |
| | FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING READING FIRE/SMOKE BARRIER?PROTECT |
| | ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE |
| | SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA |
| | 101. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND DEBRIS SHALL BE REMOVED FROM THE |
| | SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | (561) 805-6730 |
| | |
| | |
| | |