2011-08-09 15:41:491601 BELVEDERE ROAD - FLOORS 3 THROUGH 15
 PERMIT #11080065
 MASTER #11040079
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED PROVISO - SUBMIT REVISION*****
  
 THE SUBMITTED SPRINKLER DRAWINGS WERE DESIGNED IN
 ACCORDANCE WITH NFPA 13 UTILIZING RESIDENTIAL
 SPRINKLERS WITHIN THE DWELLING UNITS. THE SYSTEM WAS
 NOT DESIGNED PER NFPA 13 - RESIDENTIAL, WHICH IS
 LIMITED TO RESIDENTIAL BUILDINGS UP TO FOUR STORIES IN
 HEIGHT.
  
 LABEL THE ELEVATION OF SIDEWALL SPRINKLER (NODE 1503).
 PROVIDE RESIDENTIAL SIDEWALL SPRINKLER OBSTRUCTION
 TABLE ON PLAN (NFPA 13, 2007 EDITION - TABLE
 8.10.7.1.4) TO ENSURE CORRECT PLACEMENT OF SPRINKLERS
 (HYDRAULIC NODE 1503) WITH REGARDS TO ADJACENT SOFFIT
 OBSTRUCTION IN ALL TYPE "B" UNITS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, END OF THE LINE
 AND ARMOVERS TO PENDENT SPRINKLERS SHALL BE PROTECTED
 FROM UPWARD MOVEMENT. HANGERS SHALL BE LOCATED WITHIN
 12-INCHES OF THE DROP ELBOW. INDICATE THE METHOD TO BE
 USED FOR RESTRAINING UPWARD MOVEMENT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  