Date Text
2011-08-30 11:24:573840 HAMILTON KEY
 PERMIT #11080035
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES THIS WILL BE A CLASS A
 ADDRESSABLE SYSTEM; HOWEVER, THE EQUIPMENT PRODUCT DATA
 INDICATES THIS WILL BE A CONVENTIONAL NON-ADDRESSABLE
 SYSTEM.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER TO EACH
 FIRE ALARM DEVICE ON THE SYSTEM.
  
 DRAWINGS DO NOT REQUIRE ENGINEER?S SIGN/SEAL, BUT DO
 REQUIRE A NAME AND SIGNATURE FROM THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 NO NOTIFICATION APPLIANCES LOCATED IN FAMILY ROOM.
  
 MINI-HORN DEVICE NOT INDICATED IN SYMBOLS LEGEND.
  
 VISUAL NOTIFICATION DOES NOT APPEAR TO BE PROVIDED IN
 BEDROOMS #1, #2 OR #3.
  
 WIRE SIZE NOT INDICATED ON PLANS.
  
 BATTERY CALCULATIONS DO NOT INDICATE WHAT SIZE BATTERY
 WILL BE PROVIDED.
  
 NOTE 1: FIRE SPRINKLER FLOW SWITCH AND TAMPER SWITCH
 LOCATIONS TO BE DETERMINED; ADD DEVICES TO FIRE ALARM
 SCOPE WHEN AVAILABLE.
  
 NOTE 2: SEPARATE PERMITS WILL BE REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM AND THE SMOKE ALARMS/CARBON MONOXIDE
 DETECTORS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  