Plan Review Notes
Plan Review Notes For Permit 11080026
Permit Number 11080026
Review Stop P
Sequence Number 1
Notes
Date Text
2011-08-17 13:38:40FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 NO PLUMBING DRAWINGS WERE INCLUDED WITH THE PLANS.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 PLUMBING
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. VENTS
 7. ROOF DRAINAGE
 9. IRRIGATION
 11. GREASE TRAPS
 13. PLUMBING RISER
  
 1. SHEET A1.1 SHOWS A NEW WASH SINK AT THE NEW DUMPSTER
 ENCLOSURE AND 2 ROOF DRAINS ON THE NEW ROOF AREA.
 2. SHEET A5.1 SHOWS RE-ROUTING AN EXISTING RAIN LEADER
 ONTO A NEW ROOF AREA WITHOUT CALCULATING THE ADDITIONAL
 S.F. OF ROOF AREA FROM THE OLD ROOF.
 3. SHEET A5.3 MORE DETAIL WILL BE REQUIRED FOR THE 6"
 RWL CONNECTING TO THE S.S. GUTTER
  
 NOTE: THE NEW WASH AREA SINK SHOWN ON SHEET A1.1 WOULD
 NOT BE PERMITTED TO RECEIVE FATS OILS OR GREASE FROM
 KITCHEN WASTE UNLESS CONNECTED TO A GREASE INTERCEPTOR
  