| Plan Review Notes For Permit 11080025 |
| Permit Number |
11080025 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-09 13:11:10 | 4310 BROADWAY | | | PERMIT #11080025 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE | | | EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM | | | OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE | | | SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL | | | CLEARLY IDENTIFY THE HAZARD PROTECTED. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|