| Plan Review Notes For Permit 11080006 |
| Permit Number |
11080006 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-08-15 10:24:12 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | | | 1. REVISE EXPOSURE CATEGORY OR PROVIDE RATIONAL | | | ANALYSIS ENGINEERING FOR USE OF EXPOSURE B PRESSURES. | | | FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED | | | EFFECTIVE MARCH 1, 2009. | | | | | | 2ND REVIEW, NEW CALCS PROVIDED FOR EXPOSURE C BUT | | | INSTALLATION SCHEDULE STILL HAS DESIGN PRESSURE OF | | | 33.1. | | | | | | 2. TWO SETS REQUIRED. ONLY ONE INSTALLATION SCHEDULE | | | PROVIDED. IF TWO SETS ARE NOT PROVIDED, COPY FEES MAY | | | BE ADDED. | | | | | | ADDRESSED. WHEN RESUBMITTING, PLEASE AGAIN PROVIDE TWO | | | SETS. | | | | | | 3. THE INSTALLATION SCHEDULE PROVIDED WAS NOT COMPLETE. | | | PROPOSED ANCHOR SPACING AND SHUTTER GLASS SEPARATION | | | WERE LEFT BLANK. | | | | | | 2ND REVIEW, ANCHOR SPACING COLUMN IS STILL BLANK. | | | SHUTTER GLASS SEPARATION STATES "N/A"; SEE SHEET 1, | | | TABLE 4 FOR REQUIRED SHUTTER GLASS SEPARATION. | | | | | | |
|