| Plan Review Notes For Permit 11070768 |
| Permit Number |
11070768 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-12 16:54:15 | BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- ARCHITECT NEEDS TO SIGN AND SEAL ALL SHEETS AS | | | REQUIRED BY CHAPTER 481 FLORIDA STATUTES. ONLY THE | | | COVER SHEET OF EACH SET WAS SIGNED AND SEALED. | | | | | | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | NEW DECORATIVE HANDRAILS AT ALL RAMPS AND STEPS AS | | | REQUIRED BY SEC. 11-4.8.5 AND SEC. 11-4.9.4 FBC 2007. | | | PLANS SUBMITTED ARE MISSING THIS INFORMATION. | | | | | | 3- CURB RAMPS DETECTABLE WARNINGS NEED TO COMPLY WITH | | | SEC. 11-4.7.7. THE DETECTABLE WARNING SHALL EXTEND THE | | | FULL WIDTH AND DEPTH OF THE CURB RAMP. REVISE DRAWINGS | | | ON SHEET 3 OF 9 AS REQUIRED. | | | | | | 4- HANDICAPPED PARKING SPACE DETAIL #5 ON SHEET 3 OF 9 | | | SHOWS 16'-0" FOR THE PARKING LENGTH. NEED 18'-0" MIN. | | | REVISE AS REQUIRED. SEE ZONING REQUIREMENTS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|