| 2011-08-05 13:35:54 | 222 LAKEVIEW AVENUE - 8TH FLOOR COMMON AREA |
| | PERMIT #11070728 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS |
| | PER SECTION 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION |
| | CODE NFPA 101. THIS REQUIREMENT MAY EFFECT THE DOORS |
| | NUMBERED AS 3 & 5 OF THE SOUTHERN TENANT SPACE. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA |
| | FIRE PREVENTION CODE NFPA 101. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND DEBRIS SHALL BE REMOVED FROM THE |
| | SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | THE TWO STAIR ENCLOSURE DOORS SHALL HAVE A FIRE RATING |
| | OF AT LEAST 90 MINUTES. THE PLAN INDICATES THE TWO |
| | DOORS HAVE ONLY A 20 MINUTE FIRE RATING. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |