| 2011-08-05 15:50:53 | FBC PLUMBING 2007 REVIEW #1 |
| | DENIED: |
| | |
| | SHEET AM2 : |
| | 1. GREASE INTERCEPTOR REQUIRED |
| | 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| | REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR |
| | AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO |
| | RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH |
| | GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS, |
| | SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS, |
| | SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. |
| | FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, |
| | PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK |
| | STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE |
| | DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS |
| | WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND |
| | AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE |
| | ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS |
| | OR GREASE TO BE DISCHARGED. |
| | |
| | 2. PLEASE ADVISE AS TO THE PURPOSE OF THE BOWL SINK IN |
| | THE FRONT AREA AND THE FLOOR DRAIN IN THE BACK OPEN |
| | AREA. IF THEY RECEIVE FATS, OILS, OR GREASE THEY ARE |
| | REQUIRED TO BE CONNECTED TO A GREASE INTERCEPTOR. |
| | |
| | 3. THE F8 DRAIN SHOWN ON P-1 FOR THE 2C ICE BIN IS NOT |
| | SHOWN CONNECTED TO THE DRAINAGE ON THE ISO. OR FLAT |
| | SANITARY DRAWING. |
| | |
| | SHEET P-1 |
| | |
| | 4. WATER SUPPLY FOR 3E1 IS NOT SHOWN ON SHEET AM2 |
| | |
| | NOTE |
| | 1. 608.16.1 BEVERAGE DISPENSERS. THE WATER SUPPLY |
| | CONNECTION TO BEVERAGE DISPENSERS SHALL BE PROTECTED |
| | AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO |
| | ASSE 1022, CSA B64.3.1 OR BY AN AIR GAP. THE BACKFLOW |
| | PREVENTER DEVICE AND THE PIPING DOWNSTREAM THEREFROM |
| | SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS. |
| | |
| | 2. SHEET A1 SHOWS AN OLD GREASE TRAP . THIS WILL BE |
| | REQUIRED TO BE PROPERLY ABANDONED OR INSPECTED FOR |
| | USABILITY IF USED WITH THE NEW OCCUPANCY. |