| 2011-08-11 10:31:09 | BUILDING PLAN REVIEW |
| | PERMIT: 11070709 |
| | ADD:7900 S DIXIE |
| | CONT: MONTEIRO DEVELOPMENT |
| | TEL: (561)346-6916 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE REVIEW SITE PLAN THE ACCESSIBLE RAMP LOCATED |
| | ACROSS FROM THE ACCESSIBLE PARKING SPACES. REVIEW |
| | SECTION: 2007 FBC-B 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| | ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM |
| | OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARANCE. BOTTOM LANDING IS INDICATED AS 5FOOT |
| | WIDE. |
| | |
| | 1B) AT THE ACCESSIBLE PARKINGSPACES THE ACCESS AISLE |
| | DOES INDICATE THE USE OF DETECTABLE SURFACES BUT FROM |
| | THE BUILDING AT THE BOTTOM OF THE RAMP LANDING NO |
| | DETECTABLE WARNING |
| | SURFACES ARE INDICATED. 11-4.29.2. |
| | |
| | 2A) SHEET A3 INDICATES TTHE USE OF ROOF SCUPPERS AND |
| | SECONDARY OVER FLOW SCUPPRES BUT NO SIZE IS PROVIDED. |
| | 1504.3.2 & 1504.3.3.. |
| | |
| | 2B) THE UPPER ROOF DOES DUMP THE RAIN WATER ONTO THE |
| | LOWER ROOF SECTION PLEASE PROVIDE THE TOTAL AREA OF |
| | BOTH ROOFS IN ROOFING CALCULATION FOR THE LOWER ROOF |
| | PORTION.1504.3.3 |
| | |
| | 2C) THE RAIN LEADERS ARE NO CLEAR AS TO WHERE THEY STOP |
| | TO DRAIN ABOVE AND OVER THE SIDE WALK, OR BELOW THE |
| | SIDE WALK ENDING WHERE? 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 3) SHEET A2 DOES INDICATE A NEW COOLER AND EXTERIOR |
| | FREEZER. COOLERS AND FREEZERS ARE NOT COVERED UNDER |
| | THIS PERMIT REQUIRING SEPERATE PERMITS PLANS REVIEWS |
| | AND ASSOCIATED FEES. |
| | COOLERS AND FREEZERS WILL NEED TO COMPLY WITH 2007 |
| | FBC-B 2603.4.1.2 & 2603.4.1.3. PLEASE BE AWARE THAT |
| | EXTERIOR FREEZERS AND OR COOLERS WILL ALSO NEED TO |
| | PROVIDE PRODUCT APPROVALS INDICATING COMPLIANCE WITH |
| | 140 MPH WIND ZONE. RULE 9N-3(31)(G). |
| | |
| | 4) SHEET P1 INDICATES ROOF TOP REMOTE CONDENSING UNITS |
| | ATTACHED TO 4X4 WOOD SLEEPRES, PLEASE REVIEW 2007 FBC-B |
| | SECTION 1509.7 AND TABLE 1509.7. |
| | |
| | 5) THE PRODUCT APPROVALS SUBMITTED FOR REVIEW (WINDOWS |
| | & DOORS) ONLY ONE SEET OF APPROVALS WERE SUBMITTED, THE |
| | BUILDING DEPARTMENT REQUIRES TWO SETS ONE FOR THE FIELD |
| | AND ONE FOR RECORD RETENTION. 106.3.1. |
| | |
| | 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIE OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 6A) ROOFING ASSEMBLIES |
| | 6B) PREMANUFACTURED A/C ROOF TOP STANDS |
| | 6C) EXTERIOR FREEZERS-UNDER SEPERATE PERMIT |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |