Plan Review Notes
Plan Review Notes For Permit 11070695
Permit Number 11070695
Review Stop B
Sequence Number 1
Notes
Date Text
2011-08-10 11:20:432007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE FLOOD ZONE DESIGNATION LISTED ON THE SURVEY AND
 SHEET 101 OF THE PLANS IS INCORRECT. THE CORRECT FLOOD
 ZONE IS B. PLEASE CORRECT.
  
 2) THE PLANS SPECIFY EXPOSURE CATEGORY B ON SHEETS 306
 AND 401, HOWEVER, THE STRUCTURE IS LOCATED WITHIN 600
 FEET OF THE INTER-COASTAL WATERWAY. THEREFORE, IT IS
 CONSIDERED EXPOSURE C AND THE ROOF SHEATHING AND ROOF
 TO WALL UPLIFT LOADS ARE REQUIRED TO BE INCREASED BY 20
 PERCENT PER FBC R301.2.1.4.3. PLEASE CORRECT.
  
 3) PLEASE REVISE THE COMPONENT AND CLADDING PRESSURES
 IN THE EXTERIOR OPENING SCHEDULE TO EXPOSURE C. FBC
 R301.2.1
  
 4) FBC R 803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING SHANK NAILS.
  
 5) ROOF ZONE 3 IS NOT LISTED IN THE NAILING SCHEDULE ON
 SHEET 306. SEE FBCR FIGURE R301.2(7). PLEASE CORRECT.
  
 6) SPECIFY THE WINDOW AND DOOR BUCK TO SUBSTRATE
 ATTACHMENTS ON THE PLANS. FBC R613.6.1
  
 7) SPECIFY THE METHOD OF ATTACHMENT FROM THE PRODUCT
 APPROVAL THAT WILL BE USED TO INSTALL THE ROOF TILE AND
 RESIST THE OVERTURN MOMENT. FBC R905.3.7
  
 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 106.3.3
  
 9) THE PRODUCT APPROVAL NOAS FOR THE PGT FIXED GLASS PW
 701 AND THE ENTEGRA PLANTATION ROOF TILE HAVE BEEN
 SUPERSEDED. PLEASE SUBMIT THE CURRENT NOAS. (PW701 IS
 NOA 10-0504.05 AND ENTEGRA PLANTATION ROOF TILE IS
 10-1202.01)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]