2011-08-16 14:18:56BUILDING PLAN REVIEW
 PERMIT: 11070653
 ADD: 1701 PRESIDENTIAL WAY # 101
 CONT: SUNSHINE ALUMINUM
 TEL: (561)842-3643
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
 1) COMPLIED.
  
 2A) COMPLIED.
  
 2B) COMPLIED.
  
  
 3) THE DESIGNER OF RECORD SHALL PROVIDE THE WIND DESIGN
 CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 3.1) COMPLIED.
  
 3.2) COMPLIED.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. PLANS INDICATE AN B EXPOSURE,
 THIS UNIT BACKS UP AGAINST A GOLF COURSE SEE 2007/09
 1609.4.3 EXPOSURE C. THIS EXPOSURE SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN
 WHERE THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN
 ANY DIRECTION OF OPEN AREAS OF EXPOSURE C-TYPE TERRAIN
 THAT EXTENDS MORE THAN 600 FEET (182.9 M) AND WIDTH
 GREATER THAN 150 FT. IN THE UPWIND DIRECTION.
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3.5) POSITVE AND NEGATIVE PRESSURES FOR OPENINGS. WILL
 NEED TO BE RECALCULATED FOR C EXPOSURE.
  
 4) THE ELEVATION SHEET SUBMITTED INDICATES VERTICAL AND
 HORIZONTAL BANDS, PLEASE PROVIDE WHAT THESE ELEMENTS
 ARE, STUCCO MOLDINGS OR ARE THEY INFILL FRAMING
 MEMBERS? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) NON-HABITAL SPACE, EXISTING SLIDING GLASS DOORS ARE
 REQUIRED TO STAY IN PLACE!!!
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER