| 2011-08-08 08:23:42 | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A | | | SWITCHED RECEPTACLE OR LIGHT. AT LEAST ONE GFCI | | | PROTECTED RECEPTACLE IS REQUIRED OUTSIDE. NEC 210.70 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|