| Notes |
| Date |
Text |
| 2011-08-01 15:20:19 | ****CORRECTIONS**** | | | | | | 1. SEPARATE PERMITS REQUIRED FOR THE HOOD, OOLERS AND | | | ANSUL SYSTEM (ADVISORY ONLY). | | | | | | 2. AHU 1, GRILL SIZES NOT PROVIDED FOR THE 10" DUCTS, | | | SHEET M1.1. | | | | | | 3. UNABLE TO LOCATE FRESH AIR FOR UNIT AHU1 ON SHEET | | | M1.1. AHU2 INCLUDES A NOTE REGARDING MOTORIZED DAMPER. | | | SHEET M1.2 SHOWS INTAKE ON ROOF, BUT NO OTHER | | | INFORMATION PROVIDED, PLEASE SHOW COMPLIANCE WITH FBC | | | 13.409.AB.3.3. | | | | | | 4. SHEET M1.1, NOTE 14 REQUIRES VEF TO OPERATE AT 78, | | | M2.3 STATES FANS WILL TURN ON AT 85. PLEASE CORRELATE. | | | FBC MECHANICAL 507, EVIDENCE THAT THE FANS WILL OPERATE | | | WITH THE EQUIPMENT WILL BE REQUIRED AT INSPECTION. | | | | | | 5. THERE ARE TWO UNITS MARKED AHU2, APPEARS THAT AHU1 | | | IS MISMARKED ON SHEET M1.1. | | | | | | 6. KEY NOTES HVAC, SHEET M1.1, INCLUDE TWO NOTE 8S, TWO | | | NOTE 12S. PLEASE REVISE SO EACH NOTE HAS A UNIQUE | | | NUMBER. | | | | | | 7. THE VALUE ON THE PERMIT APPLICATION IS TO INCLUDE | | | ALL LABOR AND MATERIALS. NOTES ON SHEET M2.2 MAKE | | | REFERENCE TO ITEMS SUPPLIED BY OWNER. PLEASE INCLUDE | | | ALL LABOR AND MATERIAL, INCLUDING MATERIAL PROVIDED BY | | | OWNER. | | | | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6732 | | | | | | |
|