2011-08-01 15:20:19****CORRECTIONS****
  
 1. SEPARATE PERMITS REQUIRED FOR THE HOOD, OOLERS AND
 ANSUL SYSTEM (ADVISORY ONLY).
  
 2. AHU 1, GRILL SIZES NOT PROVIDED FOR THE 10" DUCTS,
 SHEET M1.1.
  
 3. UNABLE TO LOCATE FRESH AIR FOR UNIT AHU1 ON SHEET
 M1.1. AHU2 INCLUDES A NOTE REGARDING MOTORIZED DAMPER.
 SHEET M1.2 SHOWS INTAKE ON ROOF, BUT NO OTHER
 INFORMATION PROVIDED, PLEASE SHOW COMPLIANCE WITH FBC
 13.409.AB.3.3.
  
 4. SHEET M1.1, NOTE 14 REQUIRES VEF TO OPERATE AT 78,
 M2.3 STATES FANS WILL TURN ON AT 85. PLEASE CORRELATE.
 FBC MECHANICAL 507, EVIDENCE THAT THE FANS WILL OPERATE
 WITH THE EQUIPMENT WILL BE REQUIRED AT INSPECTION.
  
 5. THERE ARE TWO UNITS MARKED AHU2, APPEARS THAT AHU1
 IS MISMARKED ON SHEET M1.1.
  
 6. KEY NOTES HVAC, SHEET M1.1, INCLUDE TWO NOTE 8S, TWO
 NOTE 12S. PLEASE REVISE SO EACH NOTE HAS A UNIQUE
 NUMBER.
  
 7. THE VALUE ON THE PERMIT APPLICATION IS TO INCLUDE
 ALL LABOR AND MATERIALS. NOTES ON SHEET M2.2 MAKE
 REFERENCE TO ITEMS SUPPLIED BY OWNER. PLEASE INCLUDE
 ALL LABOR AND MATERIAL, INCLUDING MATERIAL PROVIDED BY
 OWNER.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER