Plan Review Notes
Plan Review Notes For Permit 11070649
Permit Number 11070649
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-08-04 15:35:39330 CLEMATIS STREET #107
 PERMIT #11070649
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 MAIN ENTRY IS PERMITTED TO BE EQUIPPED WITH PANIC
 HARDWARE OR A KEYED LOCK WITH LOCK/UNLOCK INDICATOR
 WINDOW AND SIGNAGE STATING THE DOOR IS TO REMAIN
 UNLOCKED DURING BUSINESS HOURS. A THUMB TURN LOCK IS
 NOT PERMITTED.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE
 SURFACE.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND DEBRIS IS TO BE REMOVED FROM THE
 SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 NOTE: DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  