| 2011-08-04 15:35:39 | 330 CLEMATIS STREET #107 |
| | PERMIT #11070649 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | MAIN ENTRY IS PERMITTED TO BE EQUIPPED WITH PANIC |
| | HARDWARE OR A KEYED LOCK WITH LOCK/UNLOCK INDICATOR |
| | WINDOW AND SIGNAGE STATING THE DOOR IS TO REMAIN |
| | UNLOCKED DURING BUSINESS HOURS. A THUMB TURN LOCK IS |
| | NOT PERMITTED. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE |
| | SURFACE. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND DEBRIS IS TO BE REMOVED FROM THE |
| | SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | NOTE: DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY |
| | THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS |
| | HAVE BEEN SATISFIED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |