Plan Review Notes
Plan Review Notes For Permit 11070634
Permit Number 11070634
Review Stop B
Sequence Number 2
Notes
Date Text
2011-08-12 15:07:57PROVISO
 EITHER: REVISION REQUIRED (SUBMIT INSTALLATION
 SCHEDULE) OR SUBMIT SEPARATE PERMIT FOR SHUTTERS WITH
 ALL REQUIRED INFORMATION (PRODUCT APPROVAL, PLAN,
 INSTALLATION SCHEDULE)
  
  
 SUBMIT AN INSTALLATION SCHEDULE CORRECTED AS FOLLOWS:
  
 1. SEE OPENINGS 1 AND 2, SEE SHEET 4 OF PRODUCT
 APPROVAL FOR SHUTTER TO GLASS SEPARATION REQUIRED.
  
 2. SEE SHEET 5 OF PRODUCT APPROVAL, 3 1/2" EDGE
 DISTANCE REQUIRED FOR BLOCK SUBSTRATE.
  
 3. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS ON SHEET 5 (FOR INSTANCE, 1 TOP,
 2 BOTTOM, ETC.). CODE COMPLIANCE CANNOT BE DETERMINED
 BASED ON THE INFORMATION PROVIDED.
  
  