| 2011-08-02 14:27:39 | 4050 NORTH FLAGLER DRIVE |
| | PERMIT #11070629 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1). |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING OCCUPANCY TYPE, |
| | OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY |
| | LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. |
| | INDICATE IF ANY FIRE SPRINKLER SYSTEM OR FIRE ALARM |
| | SYSTEM WILL BE PROTECTING THIS BUILDING. |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| | EDITION 2007. OCCUPANT LOADS EXCEEDING 100 PERSONS MAY |
| | REQUIRE PANIC HARDWARE. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | SEPARATE PLANS AND PERMITS REQUIRED FOR KITCHEN HOOD |
| | AND KITCHEN FIRE SUPPRESSION SYSTEM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF18' |
| | TO THE FRONT, 7?-6? TO THE SIDES AND 4? TO THE BACKSIDE |
| | PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. |
| | |
| | PROVIDE ADDITIONAL DETAILS/INFORMATION FOR THE COVERED |
| | TERRACE. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |