| Date |
Text |
| 2012-02-07 11:22:35 | 2301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3 |
| | PERMIT #11070617 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET 1-A1.0 |
| | PARTS #1128 - MEZZANINE STAIRS SHALL BE 36" WIDE |
| | MINIMUM. |
| | |
| | PROVIDE FIRE RATED SEPARATION BETWEEN PARTS (STORAGE) |
| | AND BUSINESS OCCUPANCY. PROTECT ALL OPENINGS AND |
| | PENETRATIONS. |
| | NOTE: THE RATED WALLS AND DOORS DO NOT AGREE BETWEEN |
| | PLAN SHEETS 1-A1.0 AND 1-A3.0. |
| | |
| | SHEET A1.1 |
| | PARTS #2109 - THE MEZZANINE MAY BE REQUIRED TO BE |
| | LIMITED TO 1/3 OR 1/2 THE AREA OF THE FLOOR BELOW. |
| | |
| | SHEET 1-A2.0 |
| | PROVIDE MINIMUM CEILING HEIGHT OF 7'-6". NEED VENDOR |
| | SHELVING LAYOUT TO COMPARE TO SURFACE MOUNTED CEILING |
| | LIGHT LOCATIONS. |
| | |
| | NEED AN ADDITIONAL EXIT SIGN TO LEAD TO SECONDARY EXIT |
| | IN PARTS #1128. |
| | |
| | CUSTOMER WAITING #1117 HAS EXIT SIGNS ROUTING OCCUPANTS |
| | TO A MORE HAZARDOUS OCCUPANCY. |
| | |
| | SHEET 1-A3.0 |
| | RELOCATE TABLES AND CHAIRS (NEAR TWO SOUTH DOUBLE EXIT |
| | DOORS) TO KEEP DIRECT UNOBSTRUCTED PATH TO EXITS. |
| | |
| | PROVIDE EXIT SIGN FOR PARTS STORAGE EAST EXIT AND MINOR |
| | REPAIRS AREA NORTH EXIT. |
| | NOTE: THE RCP EXIT SIGN LOCATIONS DO NOT MATCH ON |
| | SHEETS 1-A2.0 AND 1-A3.0. |
| | |
| | SHEET 1-A3.1 |
| | THE MAXIMUM OCCUPANT LOAD FOR THE BUSINESS MEZZANINE |
| | NEEDS TO BE SHOWN AS 10 PERSONS, OTHERWISE AN |
| | ADDITIONAL EXIT IS REQUIRED. |
| | |
| | SHEET 3-A5.0 |
| | INDICATE WHAT MATERIALS AND QUANTITIES OF MATERIALS |
| | WILL BE STORED IN DETAIL STORAGE #1311. |
| | |
| | GENERAL |
| | PROVIDE GUARD RAIL FOR PARTS MEZZANINE. |
| | |
| | STORAGE NEEDS TO BE MAINTAINED AT 24" BELOW THE CEILING |
| | OR STRUCTURE IN THE PARTS MEZZANINE. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |