| 2011-08-11 09:20:21 | 2301 OKEECHOBEE BOULEVARD - BUILDING 1, 2 & 3 |
| | PERMIT #11070617 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL CONFORM TO THE 2007 EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA EDITION |
| | OF NFPA 1 AND NFPA 101. |
| | |
| | PROVIDE A DETAILED SITE PLAN INDICATING FIRE DEPARTMENT |
| | VEHICLE ACCESS WIDTHS, MARKED FIRE LANES, FIRE HYDRANT |
| | LOCATIONS, PERIMETER GATES/FENCES, CONSTRUCTION |
| | TRAILERS ETC. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND DEBRIS TO BE REMOVED FROM THE |
| | SITE DAILY. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDINGS DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE BUILDING NUMBER AND BUILDING ADDRESS VISIBLE |
| | FROM THE STREET. NUMBERS SHALL BE AT LEAST SIX-INCHES |
| | IN HEIGHT AND SHALL CONTRAST THE BACKGROUND (REFERENCE: |
| | SECTION 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - |
| | NFPA 1). |
| | |
| | PROVIDE A LIFE SAFETY PLAN CLEARLY INDICATING FIRE |
| | RATED WALLS, FIRE RATED DOORS, OCCUPANT LOADS, EXIT |
| | SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON |
| | PATH OF TRAVEL, FIRE EXTINGUISHERS ETC. |
| | |
| | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2006. THE ONLY FIRE RATED |
| | SEPARATION APPEARS TO BE THE 2-HOUR FIRE BARRIER |
| | SEPARATING THE INTERIOR SERVICE BAYS FROM THE ADJACENT |
| | INTERIOR SPACE. |
| | |
| | THE SERVICE AREAS APPEAR TO BE FUNCTIONING MORE LIKE AN |
| | INDUSTRIAL/FACTORY OCCUPANCY THAN A STORAGE OCCUPANCY. |
| | |
| | INDICATE IF THE SERVICE AREAS AND BODY SHOP AREAS WILL |
| | BE FUNCTIONING AS A MAJOR OR MINOR REPAIR GARAGE AS PER |
| | SECTION 3.3.165.21.1 OF NFPA 1. |
| | |
| | NO SMOKING OR OPEN FLAME SIGNS TO BE POSTED IN ALL |
| | SERVICE AREAS, BODY SHOPS AND PAINT BOOTH AREAS. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | THE BUSINESS OFFICES (#2101, #2104 ETC.) ARE INDICATED |
| | AS BEING LOCATED ON THE MEZZANINE; HOWEVER, THIS SPACE |
| | DOES NOT MEET THE DEFINITION OF A MEZZANINE (SECTION |
| | 8.6.9 NFPA 101) WHEREBY THE MEZZANINE SPACE IS OPEN TO |
| | THE FLOOR BELOW UNLESS THE OCCUPANT LOAD OF THE |
| | AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED |
| | 10. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | HANDRAILS ARE REQUIRED TO BE INSTALLED ON BOTH SIDES OF |
| | STAIRS. |
| | |
| | SPRAYING OF FLAMMABLE LIQUIDS (PAINT) SHALL CONFORM TO |
| | THE REQUIMENTS OF NFPA 33. |
| | |
| | STORAGE AND HANDLING OF FLAMMABLE LIQUIDS SHALL CONFORM |
| | TO THE REQUIREMENTS OF NFPA 30. |
| | |
| | INDICATE THE QUANTITIES OF FLAMMABLE LIQUIDS TO BE |
| | HOUSED IN THE PAINT SHOP AND MIXING ROOM. |
| | |
| | PAINT SHOP #1304 TO BE PROVIDED WITH TWO EXITS WHEREBY |
| | ONE FIRE EVENT WILL NOT RESTRICT ACCESS TO BOTH EXITS. |
| | |
| | INDICATE THE AREAS THAT WILL BE PROTECTED BY A FIRE |
| | SUPPRESSION SYSTEM(S). |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR |
| | INSTALLATION OF FIRE SPRINKLERS, FIRE ALARMS, PAINT |
| | SPRAY BOOTHS AND ANY OTHER SPECIALTY TRADE. |
| | |
| | SHEET FA0.1 BOTH FIRE ALARM RISER DIAGRAMS INDICATED AS |
| | BUILDING #1. |
| | |
| | SHEET 1FA2.2 NOT SEALED BY ENGINEER. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |