| Plan Review Notes For Permit 11070618 |
| Permit Number |
11070618 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-15 15:08:46 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. SHEET 2P2.1 TECH RESTROOM IS FOR MEN. NO RESTROOM | | | FOR WOMEN IS SHOWN. | | | | | | 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE | | | REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR | | | EACH SEX. | | | | | | 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED | | | WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS | | | SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON | | | THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT | | | LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT | | | OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE | | | CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE | | | SEXES | | | | | | 2. SHEET P0.1 DETAIL SHOWS A SCHLER SIT-150-C OIL | | | SEPARATOR DETAIL. SHEETS 1P-2.1 & 2P-2.1 CALL FOR A | | | SEPARATOR WITH NO COLLECTION TANK. | | | | | | 3. SHEET P7.3 ROOF DRAINS SHOULD BE 8" BASED ON 5" | | | RAINFALL AND 1/8" PER FOOT FALL. THE COMBINED SECTION | | | LABELED 10,316 SHOULD BE 10" | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|