| 2011-08-09 15:20:41 | BUILDING PLAN REVIEW |
| | PERMIT: 11070618 |
| | ADD: 2311 OKEECHOBEE BLVD, BLDG# 1 |
| | CONT: NORTH AMERICAN AUTOMOTIVE SERVICES |
| | TEL: (630)352-8126 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 FBC |
| | SUPPLEMENTS |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 2007 EXST BLD CODE 601.2 CONFORMANCE. AN EXISTING |
| | BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH |
| | THAT THE BUILDING BECOMES LESS SAFE OR ENERGY EFFICIENT |
| | THAN ITS EXISTING CONDITION. IF IN THE ALTERATION THE |
| | CURRENT LEVEL OF SAFETY OR SANITATION IS TO BE REDUCED, |
| | THE PORTION ALTERED SHALL CONFORM TO THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING . |
| | |
| | 1A) SHEET 2-A1.0 THE PLANS APPEAR TO HAVE A OCCUPANCY |
| | SEPARATION WALL BETWEEN THE AUTOMOBILE REPAIR GARAGE |
| | AND MERCANTILE OCCUPANCY. IT APPEARS TO BE TWO |
| | UNPROTECTED OPENINGS IN ROOM 1213 BODY SHOP MANAGERS |
| | OFFICE? 2007/09 FBC-B TABLE 715.4. |
| | |
| | 1B) THE WALL IDENTIFIED BY TAG (N) IS NOT IDENTIFIED ( |
| | LOCATED BY ROOM # 1200 A) ON SHEET )-A1.0. THIS SHOULD |
| | BE A RATED WALL BEING A OCCUPANCY SEPARATION WALL. |
| | 2007/09 FBC-B TABLE 508.3.3. |
| | |
| | 1C) TECH LOCKER ROOM AND RESTROOM HAS WALL |
| | IDENTIFICATION TAGS IDENTIFIED BY (G) A ONE HOUR RATED |
| | WALL BUT THE DOORS LEADING INTO THESE ROOMS DO NOT |
| | INDICATE ANY FIRE RATING? PLEASE SEE 2007/09 FBC-B |
| | TABLE 715.4. |
| | |
| | 1D) LUNCH ROOM WALLS ARE IDENTIFIED BY WALL TAG (N) |
| | PLEASE PROVIDE WHAT WALL TYPE CONSTRUCTION THIS IS? |
| | |
| | 1E) PLEASE PROVIDE WALL TYPE FOR THE MAIN ELECTRIC ROOM |
| | WALLS, THEY ARE NOT IDENTIFIED. |
| | |
| | 2) SHEET 2-A6.0 INDICATES THE USE OF ? INCH OF RIGID |
| | COVER BOARD AND 2 INCHES OF POLYISO INSULATION. THE NOA |
| | 10-1018.02 PAGE 4 INDICATES THE INSULATION TO HAVE |
| | CURRENT NOA?S. |
| | |
| | 3) THE ROOFING APPROVAL 07-1018.10 DURO-LAST SINGLE PLY |
| | PVC ROOFING SYSTEMS OVER CONCRETE DECKS THIS REPORT HAS |
| | SUBSYSTEM AND WILL NEED TO CIRCLE WHICH SUBSYSTEM WILL |
| | BE INSTALLED. PLEASE REVIEW THE DESIGN PRESSURES |
| | ASSOCIATED WITH EACH SUBSYSTEM AND IF LIMITATION 7 OR |
| | LIMITATION 9 ARE APPLICABLE. IF LIMITATION 7 IS |
| | INDICATED AND ENHANCED FASTENING IS REQUIRED IN ZONES 2 |
| | & 3 PLEASE PROVIDE CALCULATIONS. |
| | |
| | 4) PLEASE REVIEW WALL SECTIONS SHEET 2-A8.0 & 2A8.1 |
| | BOTH INDICATE THE USE OF ? INCH EXTERIOR GRADE PLYWOOD |
| | FOR SHEATHING, PLEASE REVIEW: |
| | FBC-B |
| | |
| | 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL |
| | BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II |
| | CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| | ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| | REQUIRED. |
| | |
| | 5) THE ABOVE MENTIONED NOA 07-1018.10 IS FOR PVC ROOF |
| | SYSTEMS OVER CONCRETE DECKS. |
| | SHEET 2-A8.1 INDICATES NEW TOWER SECTIONS THAT WILL |
| | NEED A SEPARATE ROOFING PRODUCT APPROVAL FOR THIS TYPE |
| | OF ROOFING APPLICATION. |
| | |
| | 6) SHEET 2A-8.2 DETAIL 6 INDICATES NEW A NEW CONCRETE |
| | LINTEL FOUND ON SHEET 2A-8.3 DETAIL A, THERE IS NO SUCH |
| | SHEET LOCATED IN THE PLANS. |
| | |
| | END OF REVIEW |
| | |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |