| 2012-03-02 16:30:54 | SEPERATE ROOFING PERMIT REQUIRED SEE UNKNOWNS BELOW |
| | IDENTIFIED AS (*******) |
| | |
| | ROOFING REPORTS SUBMITTED: |
| | |
| | BERRIDGE MANUFACTURING CO ZEE-LOCK PANEL W/ CONTINUOUS |
| | CLIP |
| | NOA 10-1018.02 |
| | PAGE 5 OF 7 TABLE B FIELD -168.5 PERIMETERS & CORNER |
| | -176 PSF |
| | |
| | |
| | JOHN MANVILLE INSULATION BOARD |
| | NOA 09-0219.09 |
| | SUBSYSTEM OR TRADE NAME OF SYSTEM NOT |
| | PROVIDED.************************** |
| | |
| | |
| | DUROLAST SINGLE PLY PVC ROOF SYSTEM OVER CONCRETE DECK |
| | NOA 07-1018.10 |
| | PAGE 6 OF 14 |
| | DECK TYPE 31 |
| | SYSTEM A(2) |
| | MAX PRESSURE -247.5 LIMITATION #9. |
| | |
| | DURO-LAST SINGLE PLY PVC ROOF SYSTEM OVER WOOD DECK |
| | NOA 07-1018.14 |
| | PAGE 6 OF 10 |
| | DECK TYPE 1I |
| | SYSTEM C: |
| | MAXIMUM DESIN PRESSURES 45-60 PSF NOT IDENTIFIED |
| | LIMITATION # 7 ********************************** |
| | ******************************************************* |
| | *************************************** |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS |
| | PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). REVISIONS REQUIRE ADDITIONAL REVIEWS WITH |
| | ASSOCIATED FEES. |
| | |
| | 1) SHEET 1-A1.1 INDICATES A NEW MEZZANINE LEVEL AND |
| | HIGH RACK STORAGE SYSTEM. THE PLANS DON'T |
| | HAVE ANY DETAILS FOR THE STRUCTURAL COMPONENTS FOR |
| | EITHER SECTION. A REVISION WILL BE REQUIRED |
| | INDICATING CODE COMPLIANCE FOR BOTH OF THE AREAS. |
| | |
| | |