| Notes |
| Date |
Text |
| 2012-02-08 13:02:17 | PLANS DENIED | | | 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M) | | | MISSING FIRE DAMPERS PAGE 1-M2.1 AND 1-M2.2. | | | OF THE PLANS. | | | 2) PLEASE INDICATE ON THE PLANS WHERE THE 21X14 | | | DUCT IS GOING AND TO WHAT UNIT PAGE 1-M2.1 | | | 3) PLEASE INDICATE RATED WALLS ON THE MECHANICAL PLANS | | | 4) PROVIDE A PIPING ISOMETRIC ON MECHANICAL PLANS FOR | | | THE AIR COMPRESSOR, MO LINES WO LINES AND ATF LINES. | | | 5) THERE IS NO SUPPLY AIR IN ROOMS 1141 THROUGH 1145 ON | | | PAGE 1-M2.1 PLEASE EXPLAIN. | | | 6) INDICATE WHAT UNIT IS COOLING CAR RENTAL AREA ON | | | PAGE 3-M2.1 | | | 7) PROVIDE PRODUCT APPROVALS FOR OUT DOOR LOUVERS PER | | | SECTION | | | 106.33 2007 FBC. | | | 8) PROVIDE EXHAUST FAN NUMBERS ON EXHAUST AIR | | | CALCULATIONS. | | | 9) PROVIDE A DETAIL ON CONDENSER STAND AND CURB TO ROOF | | | TIE DOWN PER SECTION 301.12 WIND RESISTANCE 2007 FBC | | | (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|