| Plan Review Notes For Permit 11070617 |
| Permit Number |
11070617 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-02-06 12:27:36 | 11070617 | | | 2310 OKEECHOBEE BLVD. | | | NAPLETON BLDG. 1 | | | | | | THE ELECTRICAL EQUIPMENT ROOM REQUIRES TWO ENTRANCES. | | | NEC 110.26(C)(2) | | | PROVIDE DEDICATED WORKING SPACE AND SAFETY CLEARANCES | | | FOR DISTRIBUTION PANELBOARD 1DPC. NEC 110.26 | | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | | REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | | ROOMS. NEC 110.22, 110.16 | | | | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | |
|