| Plan Review Notes For Permit 11070617 |
| Permit Number |
11070617 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-17 10:44:57 | | | | BUILDING # 1 | | | RELOCATE THE MAIN BONDING JUMPER FOR BUILDING #1 TO THE | | | MAIN DISCONNECTS. NEC 250.24(B) | | | PROVIDE AN EQUIPMENT LAYOUT PLAN FOR THE COMPRESSOR | | | ROOM SHOWING THE ELECTRIC CIRCUITRY WITH DISCONNECTS | | | AND WORKING CLEARANCES. NEC 110.26, 215.5 | | | A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE SITE | | | LIGHTING. THE PLAN SHOULD INCLUDE PHOTO METRICS, THE | | | DESIGN WIND LOAD ENGINEERED FOR THE LIGHT POLES AND AN | | | ELECTRIC POWER PLAN. | | | A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE CAR WASH | | | EQUIPMENT | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | |
|